| Model |
SUN-60K-SG02HP3 -EU-EM6 |
SUN-70K-SG02HP3 -EU-EM6 |
SUN-75K-SG02HP3 -EU-EM6 |
SUN-80K-SG02HP3 -EU-EM6 |
| Battery Input Data |
|
| Battery Type |
Lithium-ion |
| Battery Voltage Range (V) |
160-1000 |
| Max. Charging Current (A) |
80+80 |
| Max. Discharging Current (A) |
80+80 |
| Charging Strategy forLi-ion Battery |
Self-adaption to BMS |
| Number of Battery Input |
2 |
| PV String Input Data |
|
| Max. PV Access Power (W) |
120000 |
140000 |
150000 |
160000 |
| Max. PV Input Power (W) |
96000 |
112000 |
120000 |
128000 |
| Max. PV Input Voltage (V) |
1000 |
| Start-upVoltage (V) |
180 |
| MPPT Voltage Range (V) |
150-850 |
| Rated PV Input Voltage (V) |
650 |
| Max. Operating PV Input Current (A) |
36+36+36+36+36+36 |
| Max. Input Short-Circuit Current (A) |
54+54+54+54+54+54 |
No. of MPP Trackers/ No. of Strings MPP Tracker |
6/2+2+2+2+2+2 |
| AC Input/Output Data |
|
| Rated AC Input/Output Active Power (W) |
60000 |
70000 |
75000 |
80000 |
| Max. AC Input/Output Apparent Power (VA) |
66000 |
77000 |
82500 |
88000 |
| Rated AC Input/Output Current (A) |
91/87 |
106.1/101.5 |
113.7/108.7 |
121.3/115.9 |
| Max. AC Input/Output Current (A) |
100/95.7 |
116.7/111.6 |
125/119.6 |
133.4/127.6 |
| Max. Continuous AC Passthrough (grid to load) (A) |
200 |
| Peak Power (off-grid) (W) |
1.5 times of rated power, 10s |
| Power Factor Adjustment Range |
0.8 leading to 0.8 lagging |
| Rated Input/Output Voltage/Range (V) |
220/380V, 230/400V 0.85Un-1.1Un |
| Rated Input/Output Grid Frequency/Range(Hz) |
50/45-55, 60/55-65 |
| Grid Connection Form |
3L+N+PE |
| Total Current Harmonic Distortion THDi |
<3% (of nominal power) |
| DC Injection Current |
<0.5% In |
| Efficiency |
| Max. Efficiency |
98.70% |
| Euro Efficiency |
98.1% |
| MPPT Efficiency |
>99% |
| Equipment Protection |
| Integrated |
DC Reverse Polarity Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Arc Fault Circuit Interrupter (optional), Anti-islanding Protection, DC Switch, Insulation Impedance Detection, Residual Current Detection |
| Surge Protection Level |
TYPE II(DC),TYPE II(AC) |
| Interface |
| Communication Interface |
RS485/RS232/CAN |
| Monitor Mode |
GPRS/WIFI/Bluetooth/4G/LAN(optional) |
| General Data |
| Operating Temperature Range (℃) |
-40 to +60℃, >45℃ Derating |
| Permissible Ambient Humidity |
0-100% |
| Permissible Altitude |
3000m |
| Noise (dB) |
≤65 |
| Ingress Protection(IP) Rating |
IP 65 |
| Inverter Topology |
Non-Isolated |
| Over Voltage Category |
OVC II(DC), OVC III(AC) |
| Cabinet Size (WxHxD mm) |
606×927×314 (Excluding Connectors and Brackets) |
| Weight (kg) |
105.0 |
| Type of Cooling |
Intelligent Air Cooling |
| Warranty |
5 Years/10 Years the Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy |
| Grid Regulation |
IEC 61727, IEC 62116,CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99,VDE-AR-N 4105 |
| Safety / EMC Standard |
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |