| Model |
SUN-5K-SG04LP3-EU-AM2-P |
SUN-6K-SG04LP3-EU-AM2-P |
SUN-8K-SG04LP3-EU-AM2-P |
SUN-10K-SG04LP3-EU-AM2-P |
SUN-12K-SG04LP3-EU-AM2-P |
| Battery Input Data |
|
| Battery Type |
Lead-acid or Lithium-ion |
| Battery Voltage Range(V) |
40-60 |
| Max.Charging Current(A) |
120 |
150 |
190 |
210 |
240 |
| Max.Discharging Current(A) |
120 |
150 |
190 |
210 |
240 |
| Charging Strategy for Li-ion Battery |
Self-adaption to BMS |
| Number of battery input |
1 |
| PV String Input Data |
|
| Max. PV Access Power (W) |
10000 |
12000 |
16000 |
20000 |
24000 |
| Max PV Input Power(W) |
8000 |
9600 |
12800 |
16000 |
19200 |
| MaxPV Input Voltage(V) |
800 |
| Start-up Voltage(V) |
160 |
| MPPT Voltage Range(V) |
200-650 |
| Rated PV Input Voltage(V) |
550 |
| Max. Operating PV Input Current (A) |
20+20 |
36+20 |
| Max. Input Short-Circuit Current (A) |
30+30 |
54+30 |
| No.of MPP Trackers/No.of String Per MPP Tracker |
2/2+1 |
2/2+2 |
| AC Input/Output Data |
|
| Rated AC Input/Output Active Power(W) |
5000 |
6000 |
8000 |
10000 |
12000 |
| Max AC Input/Output Apparent Power (VA) |
5500 |
6600 |
8800 |
11000 |
13200 |
| Peak Power (off-grid)(W) |
2 times of rated power, 10s |
| Rated AC Input/Output Current(A) |
7.6/7.2 |
9.1/8.7 |
12.1/11.6 |
15.2/14.5 |
18.2/17.4 |
| Max AC Input/Output Current(A) |
8.4/8 |
10/9.6 |
13.4/12.8 |
16.7/15.9 |
20/19.1 |
| Max Continuous AC Passthrough (grid to load)(A) |
45 |
| Rated Input/Output Voltage/Range(V) |
220/380V,230/400V 0.85Un-1.1Un |
| Grid Connection Form |
3L+N+PE |
| Rated Input/Output Grid Frequency/Range |
50/45-55, 60/55-65 |
| Power Factor Adjustment Range |
0.8 leading to 0.8 lagging |
| Total Current Harmonic Distortion THDi |
<3% (of nominal power) |
| DC Injection Current |
<0.5%ln |
| Efficiency |
|
| Max Efficiency |
97.60% |
| Euro Efficiency |
97.00% |
| MPPT Efficiency |
>99% |
| Equipment Protection |
|
| Integrated |
DC Reverse Polarity Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Arc Fault Circuit Interrupter (optional), Anti-islanding Protection, DC Switch, Insulation Impedance Detection, Residual Current Detection |
| Surge Protection Level |
TYPE II(DC), TYPE II(AC) |
| Interface |
|
| Communication Interface |
RS485/RS232/CAN |
| Monitor Mode |
GPRS/WIFI/Bluetooth/4G/LAN(optional) |
| General Data |
|
| Operating Temperature Range |
-40 to +60℃, >45℃ Derating |
| Permissible Ambient Humidity |
0-100% |
| Permissible Altitude |
3000m |
| Noise |
≤ 55 dB(A) |
| Ingress Protection(IP) Rating |
IP 65 |
| Inverter Topology |
Non-Isolated |
| Over Voltage Category |
OVC II(DC),OVC III(AC) |
| Cabinet size(W*H*D)[mm] |
422×658×254(Excluding connectors and brackets) |
| Weight[kg] |
39.8 |
| Warranty |
5 Years/10 Years the Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy |
| Type Of Cooling |
Intelligent air cooling |
| Grid Regulation |
IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G98,G99, VDE-AR-N 4105 |
| Safety EMC/Standard |
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |
| Type Of Cooling |
Intelligent air cooling |
| Grid Regulation |
IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G98,G99, VDE-AR-N 4105 |
| Safety EMC/Standard |
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |