| Model |
SUN-60K-G04P3-EU-AM4 |
SUN-70K-G04P3-EU-AM4 |
SUN-75K-G04P3-EU-AM4 |
SUN-80K-G04P3-EU-AM4 |
| PV String Input Date |
|
| Max. PV Input Power(kW) |
90 |
105 |
112.5 |
120 |
| Max. PV Input Voltage(V) |
1100 |
| Start-up Voltage(V) |
250 |
| MPPT voltage range(V) |
200-1000 |
| Rated PV Input voltage(V) |
600 |
720 |
| Max. Input Short Circuit Current (A) |
60+60+60+60 |
| Max. Operating PV Input Current(A) |
40+40+40+40 |
No. of MPP Trackers/ No. of Strings MPP Tracker |
4/3+3+3+3 |
4/4+4+4+4 |
| AC Output Side |
|
| Rated AC Output Active Power (kW) |
60 |
70 |
75 |
80 |
| Max. AC Output Apparent Power (kVA) |
66 |
77 |
82.5 |
88 |
| Rated AC Output Current (A) |
90.9/87 |
106.1/101.5 |
113.6/108.7 |
121.2/115.9 |
| Max. AC Output Current (A) |
100/95.7 |
116.7/111.6 |
125/119.6 |
133.3/127.5 |
| Rated Output Voltage/Range (V) |
220/380V, 230/400V 0.85Un-1.1Un |
| Grid Connection Form |
3L+N+PE |
| Rated Output Grid Frequency/range(Hz) |
50Hz/45Hz-55Hz 60Hz/55Hz-65Hz |
| Power Factor Adjustment Range |
0.8 leading to 0.8lagging |
| Total Current Harmonic Distortion THDi |
<3% |
| DC Injection Current |
<0.5%ln |
| Efficiency |
|
| Max. Efficiency |
98.60% |
98.70% |
| Euro Efficiency |
98.00% |
98.10% |
| MPPT Efficiency |
>99% |
| Equipment Protection |
|
| DC Reverse Polarity Protection |
Yes |
| AC Output Overcurrent Protection |
Yes |
| AC Output Overvoltage Protection |
Yes |
| AC Output Short Circuit Protection |
Yes |
| Thermal Protection |
Yes |
| Insulation Impedance Detection |
Yes |
| DC Component Monitoring |
Yes |
|
Arc Fault Circuit Interrupter (AFCI)
|
Optional
|
|
Anti-islanding Protection
|
Yes |
| Residual Current Detection |
Yes |
| Surge Protection Level |
TYPE II(DC),TYPE II(AC) |
|
DC Switch
|
Yes |
| Interface |
|
| Communication Interface |
RS485/RS232 |
| Monitor Mode |
GPRS/WIFI/Bluetooth/4G/LAN(optional) |
| General Data |
|
| Operating Temperature Range (°C) |
-25 to +60℃, >45℃ Derating |
| Permissible Ambient Humidity |
0~100% |
| Permissible Altitude (m) |
4000m |
| Noise (dB) |
≤ 55 |
| Ingress Protection(IP) Rating |
IP 65 |
| Inverter Topology |
Non-Isolated |
| Over Voltage Category |
OVC II(DC),OVC III(AC) |
| Cabinet Size (WxHxD mm) |
698×613×236.5 (Excluding Connectors and Brackets) |
| Weight [kg] |
53.7 |
| Warranty [year] |
5 years |
| Type Of Cooling |
Intelligent air cooling |
| Grid Regulation |
IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105 |
| Safety EMC/Standard |
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |